How the AWG System Works
AWG (American Wire Gauge) is a standardized system for wire sizes used primarily in North America. The numbering system runs counterintuitively: a smaller AWG number means a larger wire. This is because the original gauge system was based on the number of drawing dies required to reduce a wire to a given diameter — more draws produced a thinner wire, and each draw added a gauge number.
Key AWG facts:
- Every 3 AWG steps approximately halves the cross-sectional area (and resistance)
- Every 6 AWG steps approximately doubles the wire diameter
- AWG 4/0 (0000) is the largest standard AWG size; above that, sizes are expressed in kcmil (thousands of circular mils)
- Below AWG 40, wire becomes "magnet wire" territory used in transformers and motors
Complete AWG Reference Table
Ampacity values below are for copper THHN/THWN-2 wire in conduit, from NEC Table 310.16, 75°C column (the column applicable to most circuit terminations). Derate for ambient temperature above 30°C and for bundling per NEC 310.15. See our full ampacity derating guide for correction factor tables.
| AWG | Diameter (mm) | Area (mm²) | Nearest IEC Size | Ampacity Cu @75°C | Resistance (Ω/km) |
|---|---|---|---|---|---|
| 4/0 (0000) | 11.68 | 107.2 | 120 mm² | 230A | 0.161 |
| 3/0 (000) | 10.40 | 85.0 | 95 mm² | 200A | 0.203 |
| 2/0 (00) | 9.27 | 67.4 | 70 mm² | 175A | 0.256 |
| 1/0 (0) | 8.25 | 53.5 | 50 mm² | 150A | 0.323 |
| 1 | 7.35 | 42.4 | 35 mm² | 130A | 0.407 |
| 2 | 6.54 | 33.6 | 35 mm² | 115A | 0.514 |
| 3 | 5.83 | 26.7 | 25 mm² | — | 0.648 |
| 4 | 5.19 | 21.2 | 25 mm² | 85A | 0.816 |
| 6 | 4.11 | 13.3 | 16 mm² | 65A | 1.30 |
| 8 | 3.26 | 8.37 | 10 mm² | 50A | 2.06 |
| 10 | 2.59 | 5.26 | 6 mm² | 35A | 3.28 |
| 12 | 2.05 | 3.31 | 2.5 mm² | 25A | 5.21 |
| 14 | 1.63 | 2.08 | 2.5 mm² | 20A | 8.29 |
| 16 | 1.29 | 1.31 | 1.5 mm² | 13A | 13.2 |
| 18 | 1.02 | 0.823 | 1 mm² | — | 21.0 |
| 20 | 0.812 | 0.518 | 0.5 mm² | — | 33.3 |
| 22 | 0.644 | 0.326 | 0.35 mm² | — | 52.9 |
* Ampacity values from NEC Table 310.16, copper, 75°C column, not more than three current-carrying conductors in conduit, 30°C ambient. Derate for other conditions.
AWG vs Metric (IEC) Wire Sizes
Most of the world outside North America uses the IEC metric wire size system, measured directly in mm². The metric system doesn't have the backwards numbering quirk: a larger number is always a larger conductor. When sourcing from Chinese factories or specifying to IEC standards, you'll encounter metric sizes. The nearest equivalents are shown in the table above, but be aware:
- AWG and metric sizes don't match exactly — a 2.5 mm² conductor is close to but not identical to 14 AWG (2.08 mm²)
- For exact equivalence, always specify the actual cross-section in mm² rather than relying on "nearest equivalent"
- Medium and large conductor sizes (above 10 AWG / 6 mm²) have closer IEC equivalents than small gauge wire
Typical Applications by AWG
| AWG Range | Typical Applications |
|---|---|
| 4/0 – 1/0 AWG | Service entrance, large feeders, 200–400A panels |
| 1 – 4 AWG | Sub-panel feeders, large motor feeders, EV charging |
| 6 AWG | 50A circuits (EVSE, range, A/C), large appliances |
| 8 AWG | 40–50A circuits, dryers, water heaters |
| 10 AWG | 30A circuits, A/C units, small appliances |
| 12 AWG | 20A branch circuits, kitchen/bathroom outlets |
| 14 AWG | 15A branch circuits, general lighting |
| 16–18 AWG | Fixture leads, appliance cords, lamp wire |
| 20–22 AWG | Low-voltage control, thermostats, signal wire |
Frequently Asked Questions
What AWG wire is used for standard house wiring?
Standard US residential wiring uses 14 AWG for 15A branch circuits and 12 AWG for 20A branch circuits. Large appliance circuits use 10 AWG for 30A circuits. Service entrance for a 200A panel is typically 4/0 AWG copper or 350 kcmil aluminum.
How do I convert AWG to mm²?
Use the table above for standard sizes. The formula is: cross-section (mm²) = 0.012668 × 92^((36−AWG)/19.5). Common conversions: 14 AWG = 2.08 mm², 12 AWG = 3.31 mm², 10 AWG = 5.26 mm², 8 AWG = 8.37 mm².
What is the largest AWG wire size?
4/0 AWG (0000 AWG) is the largest standard AWG size at ~107 mm². For conductors larger than 4/0 AWG, the American system switches to kcmil (thousands of circular mils), with common sizes of 250 kcmil, 350 kcmil, 500 kcmil, and 750 kcmil used for service entrance and large feeder applications.
Factory-Direct Wire in Any AWG Gauge
Shanghai Unicorn manufactures THHN/THWN-2, XHHW-2, and specialty wire from 22 AWG through 4/0 AWG and kcmil sizes. UL listed. Direct factory pricing with volume discounts. Metric sizes and IEC constructions also available.